PQM-710 Power Quality Analyzer

21,250.00 ر.س

Available on backorder

Power Quality Analyzer
PQM-710 Sonel Poland

 

Buy it now
Brands:
SKU: PQM-710

PQM-710 Power Quality Analyzer

Model: PQM-710

Brand: Sonel

Class A remote analysis

The Sonel PQM-710 power quality analyser is a device with extended capabilities for remote analysis in class A. Sonel PQM-710 is a power quality analyser based on advanced technological solutions, with the use of which it is possible to perform comprehensive measurements, analysis and recording of 50/60 Hz power network parameters and power quality in accordance with the European standard EN 50160.

Features

  • Remote control and data transfer through a built-in GSM modem.
  • Anti-theft feature – SMS notification in the event of position change (built-in GPS receiver).
  • Real-time clock synchronized to GPS protocol.
  • Remote control of the analyzer via software: Sonel Analysis (Wi-Fi and GSM for Windows) or Sonel Analysis Mobile (Wi-Fi for Android).

Measured parameters

  • Voltages L1, L2, L3, N, PE (five measurement inputs) – average, minimum, maximum and instant values within the range up to 1000 V, interoperability with voltage transducers.
  • Currents L1, L2, L3, N (four measurement inputs) – average, minimum, maximum and instant values, current measurement within the range up to 6 kA (depending on applied current clamp), interoperability with current transducers.
  • Measurement of control signals up to 3000 Hz.
  • Crest factors for current (CFI) and voltage (CFU).
  • Frequency within the range of 40 Hz – 70 Hz.
  • Active power (P), reactive power (Q), distortion power (D), apparent power (S) with identification of the nature of reactive power (capacitive, inductive).
  • Calculation of reactive power using the Budeanu method and IEEE 1459 method.
  • Active energy (EP), reactive energy (EQ), apparent energy (ES).
  • Power factor, cosφ, tanφ.
  • K factor (transformer overload caused by the harmonics).
  • Up to 50th harmonics for voltage and current.
  • Interharmonics measured as groups.
  • Total Harmonic Distortion (THD) for voltage and current.
  • Short-term (PST) and long-term (PLT) flicker (IEC 61000-4-15 class A).
  • Unbalance of voltage (IEC 61000-4-30 class A) and current.
  • Current events detection including waveforms recording.
  • Current and voltage events recording with waveforms (up to 1 s) and RMS1/2 graphs with 30 s maximum recording time.
  • Current and voltage waveforms recording after each averaging period.

Datasheet:

Download PQM-710

More
Brand

SONEL

Compliance class

A

voltage transients (10 MHz sampling)

No. of Voltage / No. of Current

5 / 4

V /I THD and harmonics

V / I TID and interharmonics

Angles between harmonics

K-factor / Mains signaling

Maximal recording time

100 years

Wi-Fi / GSM (UMTS) modem

Battery operating time

min. 2 h

Display

LCD display

Dimension (mm)

200x175x75

Weight (Kg)

1.6